Transformer Series STA
13911E00

Transformer

Series STA

  • Advantages using a control transformerLow voltage drop in switching inductive loadsFlexible voltage adjustment by primary tapping (±5%)Limitation of short-circuit current in control circuitTypical applicationsControl voltage circuitsFunctional extra-low voltage PELVSafety extra-low voltage SELVProtective separation (of circuits)
Introduction Data sheets Certificates

The application of a control transformer is demanding EN 60204-1 for control circuits (few exceptions).The protection of transformers has to be primary with a Motor protection circuit-breaker in tripping class 10 or 10 A. Our circuitbreaker (Type 8523/8.) will be adjusted according the current rating of the transformer (see attached table). Secondary a miniature fuse or a MCB should be used.

The criterions are:

  • Protective measures against direct or indirect contact (see also IEC 60364-4-43)
  • Line protection
  • Overload protection of switching devices (welding of contacts)
  • All electrical settings of control circuit according to manufacturers' instructions

A minimum distance of 40 mm to all other components has to be kept.